ARCHIVED – NEB SA 2005-03 Programmable Logic Controller (PLC) Failure
This page has been archived on the Web
Information identified as archived is provided for reference, research or recordkeeping purposes. It is not subject to the Government of Canada Web Standards and has not been altered or updated since it was archived. Please contact us to request a format other than those available.
NEB SA 2005-03 Programmable Logic Controller (PLC) Failure [PDF 198 ko]
File AFMSA-INC-2005 48
23 December 2005
To: All companies under National Energy Board jurisdiction
Canadian Energy Pipeline Association
Canadian Association of Petroleum Producers,
and provincial regulators
Subject: National Energy Board Safety Advisory
NEB SA 2005-03
Attached is a safety advisory regarding the hazards associated with the possible ramifications of a programmable logic controller (PLC) failure. The Board expects that this advisory be given wide circulation to personnel involved in maintenance and pipeline operations within your organization.
If you have any questions regarding this Advisory, please contact us toll free at 1-800-899-1265.
Yours truly,
Mary Lou Scharf
for
Michel L. Mantha
Secretary
Attachment
Safety Advisory
NEB SA 2005-03
23 December 2005
Programmable Logic Controller (PLC) Failure
Incident Description
In October 2005, a programmable logic controller (PLC) controlling the compressor unit failed. Immediately after the failure, the suction and discharge valves closed, but the electric motor for the unit continued to operate and went into surge. This resulted in excessive vibration of the piping, severing a NPS 2 load and purge line at the flange connection outside the compressor building. Approximately 25 minutes after the PLC failure, the motor experienced an explosion. The venting of gas from the two inch pipe and the subsequent explosion caused considerable damage to the facility.
Preliminary Observations
The incident is under investigation by the National Energy Board and the Transportation Safety Board. At this point, it appears that the low signal generated by the PLC at the time of failure did not trip the breaker feeding the motor allowing the motor to continue to operate against closed valves and begin to surge. All other systems had shut down, including the lube oil system, which allowed the compressor seals to dry out. Natural gas may have entered the compressor motor via the compressor seals where an ignition source was present.
Preventive Actions
Failure of PLCs may not result in a fail safe condition. In the above case, the motor continued to operate after the suction and discharge valves closed resulting in overheating of the compressor, excessive vibration and eventual failure of the NPS 2 load and purge line, and an explosion within the motor casing.
Breaker operations should be tested regularly to ensure breakers function appropriately for all foreseeable failure modes including PLC failure.