Inspection Officer Order No. DJM-001-2022
Inspection Officer Order No. DJM-001-2022 [PDF 518 KB]
IN THE MATTER OF THE CANADIAN ENERGY REGULATOR ACT,
AN ORDER UNDER SECTION 109
COMPANY TO WHOM THIS ORDER IS DIRECTED
NOVA Gas Transmission Ltd. (NGTL) is a company conducting work associated with a regulated facility located near Dawson Creek, British Columbia as part of the NGTL Groundbirch Mainline Loop – Sunrise Section.
On or about 29 November 2022 at 12:00 PM the undersigned Canada Energy Regulator Inspection Officer conducted a compliance verification activity (CVA 2223-171) of NGTL Groundbirch Mainline Loop - Sunrise Section.
RELEVANT FACTS
I, , designated as a CER Inspection Officer under subsection 102(1) of the Canadian Energy Regulator Act (CER Act), believe the following are the relevant facts relating to the issuance of this Order:
- NGTL failed to demonstrate an effective method of work inspection was occurring, noting many hazards specific to the chemical solvent, Methyl Ethyl Ketone (MEK), were not under control as required by project approval certificate conditions and provincial occupational health and safety regulation, during pipeline construction operations.
- Safety controls including but not limited to, required for the safe transport, use, handling, and storage of MEK, including application of WHMIS, management of potential ignition sources, ensuring potential worker exposure has been assessed and is controlled, decanting, grounding and bonding of containers, Respiratory Protective Equipment (RPE) and other Personal Protective Equipment (PPE) as identified in the Safety Data Sheet (SDS), was not in use or being adequately applied.
- Previous CER enforcement actions including Notice of Non-Compliance and Corrected Non-Compliance, were issued relative to industrial hygiene matters during compliance verification activities CV2122-188 and CV2122-183, with failure to ensure the safety of persons engaged in coating operations.
PROVISIONS OF ACT OR REGULATIONS THAT ARE ALLEGED TO BE CONTRAVENED – AND ARE CONTINUING – OR ARE LIKELY TO BE CONTRAVENED
Canadian Energy Regulator Act: Reasonable care. (94) The holder must take all reasonable care to ensure the safety and security of persons, the safety and security of regulated facilities and abandoned facilities and the protection of property and the environment.
MEASURES TO BE TAKEN
Based on the facts referenced herein, where the Inspection Officer has reasonable grounds to believe that there is or is likely to be a contravention of Parts 2 to 5 or section 335 of the CER Act, or for a purpose referred to in subsection 102(2) CER Act, the Inspection Officer may, by order, direct a person to
- stop doing something that is in contravention of Parts 2 to 5 or section 335 or cause it to be stopped;
- take any measure that is necessary in order to comply with Parts 2 to 5 or section 335 or mitigate the effects of non-compliance;
- stop doing something that may cause a hazard to the safety or security of persons, or damage to property or the environment or cause it to be stopped; or
- take any measure that is necessary to prevent or mitigate the hazard to the safety or security of persons or damage to property or the environment.
NGTL is ORDERED pursuant to subsections 109(1) and 109(2) of the CER Act to:
SPECIFIED MEASURES:
- Cease the use of the observed CRC-Evans, pipeline coating application system, until a method of competent construction inspection, through the utilization of training, knowledge, and expertise, of the components, the use, and operation of the coating system, can be demonstrated to the Inspection Officer.
- Provide assurance that those assigned the responsibility of General, Safety or Coating inspection, on behalf of NGTL, can demonstrate compliance with WHMIS requirements (as required by Condition 2 of Order XG-029-2019 and the Construction Safety Manual).
- Provide to the Inspection Officer for review, an exposure control plan specific to the Methyl Ethyl Ketone liquid, and relevant other hazardous chemicals used in coating.
- Demonstrate that NGTL has reviewed the applicability of Management of Change (MOC), or a Hazard Analysis, of the CRC-Evans spray coating system, and provide to the Inspection Officer for review a summary of the key safety hazards and the management controls for MEK and other pipeline coating chemicals.
- Provide a Corrective and Preventative Action Plan, noting systemic actions that will prevent recurrence, and detailing time to completion of Measures 1-4, to the Inspection Officer for review.
EFFECTIVE DATE OF THE ORDER
This Inspection Officer Order takes effect immediately on 02 December 2022 at the time of delivery of this Order to the person/company to whom it is directed. Nothing in this Order shall be construed as reducing, increasing, or otherwise affecting what may be required of the person/company to whom it is directed to comply with all applicable legislative or legal requirements.
COMPLIANCE WITH THIS INSPECTION OFFICER ORDER IS MANDATORY
Failure to comply with an Inspection Officer Order issued under section 109 of the CER Act is an offence under section 112 of the CER Act.
Inspection Officer |
__________________________________ Signature |
|
IO Designation Number | ||
02 December 2022 |
__________________________________ Name (printed) |
|
Date | ||
210-517 10 Ave SW, Calgary AB T2R 0A8 |
Please note that
- in compliance with the CER’s Enforcement Policy, this Order will be posted on the CER’s website.
- All submissions to the CER in response to the order are to be provided within the CER Operations Regulatory Compliance Application (ORCA) quoting the associated CVA #, Inspection Officer Order #, and any specific measure with which the submission is associated.
CVA or Incident #: CV2223-171